Permit Number: T21CM05862
Parcel: 106060180

Address:
1280 W PRINCE RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM05862
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/28/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A1; Code Review (Plumbing Fixtures): The Code Review indicates "service sink and point-of-use drinking fountain provide". Please indicate on the Floor Plan (Sheet A3) the location of those fixtures.
2. Sheet A3 (Floor Plan); Door Schedule: Please indicate on the Floor Plan the door type for each door listed on the Door Schedule. Provide header and jamb details for each new door.
3. Sheet A3; Floor Plan: The detail indicators at the new partition walls reference 1/A6. Please revise that reference.
4. Sheet A3; Floor Plan: Please indicate the wall type on the plan as indicated in the Wall Legend.
5. Sheet A3; Floor Plan: The new corridor does not meet the requirements of the IBC Section 1020.4 Exception 2. The dead end corridor exceeds the allowable 50' maximum length. Please verify.
6. Sheet A4; Reflected Ceiling Plan: Please provide exit light locations on this plan. Add directional exit lighting as required due to the addition of the new corridor.
7. General: Please provide written responses to all review comments.
07/29/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Revise the reflected ceiling plan to show the HVAC returns. Verify that the dead-end corridor is not acting as a duct. Reference: Section 601.2, IMC 2018 and Section1020.4, exception 2, IBC 2018.
07/29/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
07/29/2021 JVINCEN1 FIRE REVIEW Approved
07/29/2021 ROBERT SHERRY WATER REVIEW Completed
08/04/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
08/12/2021 SBLOOD1 ENGINEERING REVIEW Passed
08/13/2021 STEVE SHIELDS ZONING REVIEW Approved
08/13/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed