Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T21CM05854
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/10/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet 23 of 25; PZSE,Inc. Engineering Certification: This report indicates the Unirac U-Builder 2.0 Solarmount flush rail is compliant with the listed codes on that sheet. It also indicates that this Certification excludes the evaluation of the following: A. The structure to support loads imposed by the new array. B. Attachment of the rails to the existing support structure. Please provide the structural calculations indicating the various items listed above are capable of supporting the new module loads. |
| 08/11/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments and provide a written response. 1. Provide plans sealed by a Arizona Registrant. Ref; 2018 IBC sec. 107.2.1, 2018 NEC, City of Tucson Commercial Plan Submittal Requirements. |
| 08/16/2021 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 08/16/2021 | SSHIELD1 | ENGINEERING | REVIEW | Passed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/16/2021 | NGARCIA3 | OUT TO CUSTOMER | Completed |