Permit Number: T21CM05854
Parcel: 136151110

Review Status: Completed

Review Details: OTHER

Permit Number - T21CM05854
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/10/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet 23 of 25; PZSE,Inc. Engineering Certification: This report indicates the Unirac U-Builder 2.0 Solarmount flush rail is compliant with the listed codes on that sheet. It also indicates that this Certification excludes the evaluation of the following:
A. The structure to support loads imposed by the new array.
B. Attachment of the rails to the existing support structure.
Please provide the structural calculations indicating the various items listed above are capable of supporting the new module loads.
08/11/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments and provide a written response.

1. Provide plans sealed by a Arizona Registrant.

Ref; 2018 IBC sec. 107.2.1, 2018 NEC, City of Tucson Commercial Plan Submittal Requirements.
08/16/2021 SSHIELD1 ENGINEERING REVIEW Passed
08/16/2021 STEVE SHIELDS ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/16/2021 NGARCIA3 OUT TO CUSTOMER Completed