Permit Review Detail
Review Status: Active
Review Details: COMMERCIAL - TI
Permit Number - T21CM05816
Review Name: COMMERCIAL - TI
Review Status: Active
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/16/2021 | ANY | ENGINEERING | REVIEW | Active | |
07/28/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A-1; Key Note 5: Please provide details for the new mechanical door, including support framing, bracing, and connections to existing structure. 2. Sheet A-1; Floor Plan: Please provide a more complete floor plan, indicating shelving, check-out areas, storage racking, etc. 3. Sheet A-1; Floor Plan: It appears a stair is indicated at the north end of this tenant space. Please provide a mezzanine plan in the drawings, indicating the SF, construction type, and occupant load. Verify on the drawings the requirements of the IBC Section 505 are met. 4. General: Please provide written responses to all review comments. |
07/28/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
07/28/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
07/28/2021 | ROBERT SHERRY | WATER | REVIEW | Completed | |
07/30/2021 | JVINCEN1 | FIRE | REVIEW | Reqs Change | See building comments. |
08/03/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
08/12/2021 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
08/12/2021 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |