Permit Number: T21CM05814
Parcel: 10605009L

Address:
635 W ROGER RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM05814
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/04/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM05814

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
Conditionally Approved

BUILDING REVIEW COMMENTS:
Approved

MECHANICAL REVIEW COMMENTS:
Denied
1. Correction not complied you have not put in the ventilation calc table the exhaust required for room 101 and you have not clouded on your mechanical plans the correction for that room101. Their is nothing in your response that address this.
ELECTRICAL REVIEW COMMENTS
Conditionally Approved

PLUMBING REVIEW COMMENTS:
Approved
10/11/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM05814
635 W Roger Rd – I-1
Humane Society - Education & Outreach Facility

TRANSMITTAL: October 11, 2021
This site is located in I-1 zone (UDC Article 4.7.29), Animal Services is an allowed use in the zone (Table 4.8-5), subject to Use Specific Standard 4.9.13.Q.

1. Zoning has reviewed the building plans for compliance with DP21-0183 and although the building plans appear to match the DP until the revision to the DP is approved Zoning cannot approved this plan.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.
10/20/2021 SBLOOD1 ENGINEERING REVIEW Approved