Permit Number: T21CM05814
Parcel: 10605009L

Address:
635 W ROGER RD

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T21CM05814
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/29/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM05814

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
Denied
1. Geotechnical Report for the proposed building is not submitted per International Building Code 2018, Section 1803.1. Inspector to verify all info used on Structural Drawings and Structural Calculations against the Geotechnical Report.
2. Non-load bearing walls require a deflection track or details to allow for the relative lateral deflection of the structural members.

BUILDING REVIEW COMMENTS:
Denied
1. The occupant load breakdown is confusing. Provide a clear breakdown that clearly indicates the occupant loads for each building.

MECHANICAL REVIEW COMMENTS:
Denied
1. Provide exhaust to training room #101 (IMC2018,403.3.1.1)

ELECTRICAL REVIEW COMMENTS
Denied
E1.1 Elec. HVAC Power Plan: Confirm conductor size for ERV-1 is large enough or upsize.
E2.0 Lighting Plan: Note 4: Catio? Patio?
E4.0 Panel Schedules: Panel B, circuit 37,39,41 is mislabeled and should be ERV-3. Power loads not shown for circuit either.

PLUMBING REVIEW COMMENTS:
Approved
08/04/2021 ROBERT SHERRY WATER REVIEW Completed
08/10/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM05814
635 w Roger Rd – I-1
Humane Society – Education & Outreach Facility

TRANSMITTAL: August 10, 2021
This site is located in I-1 zone (UDC Article 4.7.29), Animal Services is an allowed use in the zone (Table 4.8-5), subject to Use Specific Standard 4.9.13.Q.

1. Zoning reviewed the building plans for compliance with DP21-0183 and the proposed building does not match what is shown on the DP. A DP that matches the proposed building will need to be submitted and approved prior to approval of the building plans.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz
08/10/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
08/16/2021 SBLOOD1 ENGINEERING REVIEW Reqs Change See zoning comment on need for a matching approved DP.

Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov
08/20/2021 JVINCEN1 FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/20/2021 NGARCIA3 OUT TO CUSTOMER Completed