Permit Number: T21CM05761
Parcel: 12416149A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM05761
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/22/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
07/27/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide a site plan that shows the location of the building on the site with the distances from the building to the lot lines drawn in accordance with an accurate boundary line survey. Reference: Section 107.2.6, IBC 2018.
2. Show how the proposed termination of the exhaust fan, EF-1, complies with requirements of Section 506.3.13.3, IMC 2018.
3. Verify that combustible beams supporting the hood comply with Section 507.2.6, IMC 2018 for clearances (i.e. 18-inches).
07/27/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Revise the size of the natural gas pipe serving the 4-Burner Range (15) per Table 402.4 (2). Reference: Section 402.4, IFGC 2018
07/27/2021 ROBERT SHERRY WATER REVIEW Completed
07/29/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
07/30/2021 JVINCEN1 FIRE REVIEW Approved
08/09/2021 STEVE SHIELDS ZONING REVIEW Approved
08/09/2021 SSHIELD1 ENGINEERING REVIEW Passed
08/09/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed