Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T21CM05736
Parcel: 10612017P

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM05736
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/21/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
07/22/2021 ROBERT SHERRY WATER REVIEW Completed
07/22/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Show that the specified design of the water closet seats meet the requirements of Section 425.3, IPC 2018 (i.e. open-front seat).
2. A common vent is limited to serving two traps or trapped fixtures. Reference: Section 911.1, IPC 2018.
3. Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018.
07/26/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
07/29/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
08/09/2021 SSHIELD1 ENGINEERING REVIEW Passed
08/09/2021 STEVE SHIELDS ZONING REVIEW Approved
08/09/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/17/2021 JPEELDA1 FIRE REVIEW Approved