| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/21/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 07/22/2021 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 07/22/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Show that the specified design of the water closet seats meet the requirements of Section 425.3, IPC 2018 (i.e. open-front seat). 2. A common vent is limited to serving two traps or trapped fixtures. Reference: Section 911.1, IPC 2018. 3. Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018. |
| 07/26/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 07/29/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 08/09/2021 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
| 08/09/2021 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 08/09/2021 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 08/17/2021 | JPEELDA1 | FIRE | REVIEW | Approved |