Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T21CM05726
Parcel: 140294950

Review Status: Completed

Review Details: OTHER

Permit Number - T21CM05726
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/02/2021 PCAMARE1 OIP REVIEW Reqs Change FROM: Paul Camarena
PDSD Residential Review Section

PROJECT: T21CM05726
Roof top Solar Panels (1st Review)
6320 S DESERT RANGE CT

TRANSMITTAL DATE: August 2, 2021



COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Residential Review Section comments were addressed.


o COMMENT: Residential has reviewed the plan and cannot approve at this time. Please address the following comments.


o COMMENT: This plan set is not compliant with the Fire code, demonstration compliance to 2018 International Fire Code 1204.2.1.1. If the slope of the building is greater than 2:12 then compliance must be shown on the plans. Show a 36" wide access pathway from the eave to the ridge on both sides of the building.


o COMMENT: Residential will review the application on the next submittal




If you have any questions about this transmittal, Contact Paul Camarena any time during the week by email Paul.camarena@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans

Final Status

Task End Date Reviewer's Name Type of Review Description
08/02/2021 VVERA1 OUT TO CUSTOMER Completed