Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T21CM05716
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/21/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet c0.01; Building Codes: Please replace the 2018 International Residential Code to the 2018 International Building Code. 2. Sheets as0.01 and a1.01: Both of these sheets indicate "Preliminary Not For Construction" over the registered design professional's seal. Please revise. |
| 07/22/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide construction documents that are complete and clearly indicate the extent of the proposed work (i.e. remove the “Preliminary, not for Construction” label from the drawings.). Reference: Section 107.2.1, IBC 2018. 2. Verify that there is sufficient heat for the individual dwelling units to maintain a minimum temperature of 68?F on a design heating day (32?F). Portable heating or cooking appliances may not be used for this requirement. Reference: Section 309.1, IMC 2018. 3. Verify that mechanical cooling equipment capable of producing ambient temperatures at or below 82 degrees Fahrenheit is present and operable in each dwelling unit. Reference: Section 16-11(b), Tucson, AZ Code of Ordinances. |
| 07/22/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 07/22/2021 | ROBERT SHERRY | WATER | REVIEW | Passed | |
| 07/29/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 08/09/2021 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
| 08/09/2021 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 08/09/2021 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 08/19/2021 | JVINCEN1 | FIRE | REVIEW | Approved |