Permit Number: T21CM05707
Parcel: 138202040

Address:
422 W INEZ DR

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T21CM05707
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/07/2021 PCAMARE1 OIP REVIEW Reqs Change FROM: Paul Camarena
PDSD Residential Review Section

PROJECT: T21CM05707
Roof top Solar Panels (1st Review)
422 W INEZ DR

TRANSMITTAL DATE: September 7, 2021



COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Residential Review Section comments were addressed.


COMMENT: Residential has reviewed the plan and cannot approve at this time. Please address the following comments.


COMMENT: It appears that on three line diagram there is a 40A PV Breaker and on the single line diagram there is a 30A PV Breaker. Please correct the plan set to show the correct breaker.

COMMENT: Residential will review the application on the next submittal




If you have any questions about this transmittal, Contact Paul Camarena any time during the week by email Paul.camarena@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans

Final Status

Task End Date Reviewer's Name Type of Review Description
09/07/2021 VVERA1 OUT TO CUSTOMER Completed