Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T21CM05658
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/16/2021 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | FROM: PDSD Zoning Review PROJECT: T21CM05658 5613 E 2nd St – R-1 Detached Storage Container (2nd Review) TRANSMITTAL: August 16, 2021 This site is located in the R-1 zone (UDC 4.7.1). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9. 10. None of the following comments were addressed. 1. Provide a residential plot plan that meets the requirements found at: https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf. 2. Per UDC Article 6.6.3.B Detached accessory buildings are not permitted in the buildable area extending the full width of the lot between the principal building and the front street lot line. The proposed storage container is not allowed in the front yard and will require a Board of Adjustment for Variance as shown on the plan. Board of Adjustment application and requirements can be found at: https://www.tucsonaz.gov/files/pdsd/codes/Zoning_Administration_Application_BA_fillable.pdf. The Board of Adjustment is a separate submittal from this building plan and is submitted at: https://www.tucsonaz.gov/pdsd-filedrop, using the “Submission Type”, “Zoning Administration”. Contact Mark Castro at Mark.Castro@tucsonaz.gov with any questions about the Variance process. 3. Per UDC TABLE 6.3-2.A: DIMENSIONAL STANDARDS FOR THE R-1, R-2, R-3, MH-1, & MH-2 ZONES, R-1 Zone the required interior perimeter yard setback is 6’-0” or 2/3 the height of the exterior wall, greater of the two. Based on a typical storage container height of 8’-0” the required perimeter yard setback to the west property line is 6’-0”, proposed is 0’-0”. 4. Per UDC Article 6.4.5.C.1.a Within established areas , the minimum required front street perimeter yard is 20 feet or one and one-half the height of the proposed wall (H), measured from the street property line. Based on a typical storage container height of 8’-0” the required street perimeter yard setback is 20’-0”. As the property lines are not shown correctly the proposed street perimeter yard setback cannot be verified. The plans show the street property line south of the sidewalk which is not correct. The street property line should be shown 12’ north of the face of curb along 2nd St. 5. As you are proposing a reduced setback less than 1’-0” to the west property a Board of Adjustment for Variance is required. The accessory structure and setbacks can be processed under the same Variance. If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov. |