Permit Number: T21CM05617
Parcel: 12701005D

Review Status: Completed

Review Details: OTHER

Permit Number - T21CM05617
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/02/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following Electrical plan review comments. Also provide a written response.

Provide Sealed electrical plans, design and calculations performed by an Arizona registrant who has demonstrated proficiency through registration, education, technical knowledge, or experience to perform such work.

Include load calculations ,complete panel schedules, power source.

Ref; 2018 IBC 107.2.1, 2017 NEC. City of Tucson Commercial Plan/Permit Submittal Requirements. 2012 Tucson/Pima County Outdoor Lighting Code.
08/04/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Revise the drawings to comply with the requirements of the approved Appeal to the Building Official. The installation of a bottle filler in lieu of a drinking fountain requires the installation of a permanently mounted disposable cup dispenser. A cup dispenser shall be located adjacent to each bottle filler with the dispensing end between 34” and 48” above the finished floor.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/04/2021 VVERA1 OUT TO CUSTOMER Completed