Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T21CM05617
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/02/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following Electrical plan review comments. Also provide a written response. Provide Sealed electrical plans, design and calculations performed by an Arizona registrant who has demonstrated proficiency through registration, education, technical knowledge, or experience to perform such work. Include load calculations ,complete panel schedules, power source. Ref; 2018 IBC 107.2.1, 2017 NEC. City of Tucson Commercial Plan/Permit Submittal Requirements. 2012 Tucson/Pima County Outdoor Lighting Code. |
| 08/04/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Revise the drawings to comply with the requirements of the approved Appeal to the Building Official. The installation of a bottle filler in lieu of a drinking fountain requires the installation of a permanently mounted disposable cup dispenser. A cup dispenser shall be located adjacent to each bottle filler with the dispensing end between 34” and 48” above the finished floor. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/04/2021 | VVERA1 | OUT TO CUSTOMER | Completed |