Permit Number: T21CM05570
Parcel: 110111370

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM05570
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/06/2022 NMARTEL1 ZONING REVIEW Reqs Change PDSD TRANSMITTAL FROM: PDSD
Zoning Review
PROJECT: T21CM05570
4942 E Bermuda st
Proposed Detached Carport (2nd Review)
01/07/2022

The residential plans have been reviewed by the Zoning Review Section but cannot be approved until all zoning comments or concerns have been addressed.

1. The storage container on the east side of the property is not permitted, and does not meet the side perimeter yard setback. Please add a setback measurement for the structure. Zoning cannot tell if the structure is attached or detached from the house. If detached, a neighbor waiver can be added to the site plan to reduce the required side yard setback. If it is attached, engineered drawings may be required, and a Design Development Option (DDO) would be necessary to reduce the required setback.

2. Provide the setback measurement for the attached carport as measured to the east property line. A DDO may be required to reduce the required setback (6' or 2/3 the height of the structure)
3. The carport does not meet front street perimeter yard setbacks. A DDO is necessary to reduce the front street setback.
4. The same DDO may be used to reduce all perimeter yard setback in question. Please reach out to Mark.Castro@tucsonaz.gov for more information about the DDO process.
5. Please attach the elevation plans from the first submittal to the next submittal. Add the directions for each side of the structure.
6. Add a legal description to the site plan. The legal description for the propert is: "GLENN HEIGHTS LOT 137"
7. Add the site zoning and surrounding zoning on the site plan.
8. All the requirements of a site plan can be found on this example: https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf

To resubmit your plans for additional review, please visit: https://docs.tucsonaz.gov/Forms/tucsonpermitapp. If you have any questions about this transmittal, please contact me at Nicholas.Martell@tucsonaz.gov
01/12/2022 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T21CM05570
PLAN REVIEW COMMENTS
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide an updated complete plan set with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.
GENERAL REQUIREMENTS:
The City of Tucson adopted the 2018 IRC with amendments on 1/1/2019. Show the current code reference on the plans.
Consolidate pages of construction plans into a single .PDF file as prescribed at the PDSD web site. https://www.tucsonaz.gov/pdsd/online-permits
Sample plans are available at https://www.tucsonaz.gov/pdsd/residential-permits
GENERAL COMMENTS:
1. Complete Zoning issues then show necessary structural documentation for achieving building code compliance, 2018 IRC.

SITE PLAN:
1. Indicate the location of buildings and any utilities supporting or effecting the proposed structure.

FOUNDATION PLAN:
1. Dimension the footing length, width, and depth into undisturbed soil for each footing type and condition, R403.1. Show the minimum 12" reinforced footing depth below the undisturbed ground surface R403.1. Show rebar reinforcement with 3" clearance from earth, R403.1.3.5.3. Provide ½" anchor bolts with 7" embedment, R403.1.6.

FRAMING PLAN:
1. Provide a complete roof framing plan with beams and rafters sized with appropriate load carrying capacity, R301.1.

SECTIONS - DETAILS:
1. Show the Post Section Detail with #4 rebar in the footing, R403.1.
2. Notate and specify the size of post base with 1” standoff above concrete, R317.1.4 exception 1.
3. Show roof (uplift resistance) rafter fasteners (H2.5) with appropriate uplift capacity, R802.11 amended.
4. Show connection at dwelling with fasteners (rafter on top plate with H2.5 or ledger connection to load bearing wall).

Please contact the plans reviewer if you have any questions:
Ken Van Karsen
520 837-4912
City of Tucson Residential Plan Review