Permit Number: T21CM05565
Parcel: 113071770

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T21CM05565
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/04/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change Each dwelling unit building requires a separate Pima County assigned street address, R319. Notate each dwelling address on the site plan.

Exterior walls with a fire separation distance less than 3-foot to a private property line require not less than one-hour fire-resistive construction. Show compliance with R302.1 (City of Tucson Amended) by providing a section detail of materials prescribed in IBC Table 721.1(2), Items 15-1.1 to 16-1.3.
08/06/2021 SBLOOD1 ENGINEERING REVIEW Passed
08/06/2021 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: T21CM05565
3046 N Mountain Ave – R-2
Remodel Duplex (1st Review)

TRANSMITTAL DATE: August 6, 2021

This site is located in the R-2 zone (UDC 4.7.9). Multi-family residential is a permitted use in this zone (Table 4.8-2). See Use Specific Standards 4.9.7.B.6, .9 & .10

1. As these plans show remodels to both sides of the duplex two (2) separate permits and addresses are required.


If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
08/06/2021 NGARCIA3 OUT TO CUSTOMER Completed