Permit Number: T21CM05555
Parcel: 117033090

Address:
721 N 4TH AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM05555
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/19/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
07/21/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Revise the mechanical design as required to avoid using the corridor as a return air duct (i.e. provide a return from the breakroom to FC-2). Reference: Section 601.2, IMC 2018.
07/21/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
07/21/2021 ROBERT SHERRY WATER REVIEW Passed
07/28/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Provide compliance with the 2018 IECC for the lighting.
Ref; 2018 IECC , City of Tucson Commercial Plan submittal requirements.
07/29/2021 JVINCEN1 FIRE REVIEW Approved
08/02/2021 STEVE SHIELDS ZONING REVIEW Approved
08/02/2021 SSHIELD1 ENGINEERING REVIEW Passed
08/02/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed