Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T21CM05555
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/19/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
07/21/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Revise the mechanical design as required to avoid using the corridor as a return air duct (i.e. provide a return from the breakroom to FC-2). Reference: Section 601.2, IMC 2018. |
07/21/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
07/21/2021 | ROBERT SHERRY | WATER | REVIEW | Passed | |
07/28/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Provide compliance with the 2018 IECC for the lighting. Ref; 2018 IECC , City of Tucson Commercial Plan submittal requirements. |
07/29/2021 | JVINCEN1 | FIRE | REVIEW | Approved | |
08/02/2021 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
08/02/2021 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
08/02/2021 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |