Permit Number: T21CM05553
Parcel: 12606200A

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T21CM05553
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/22/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM05553

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
Approved

BUILDING REVIEW COMMENTS:
Denied
1. The plans indicate that a sprinkler system is being installed. Is this just the expansion into the new space? Is there an existing alarm system? Ambulatory care facilities. Provide a narrative on the alarm system plans. Ambulatory care facilities require an alarm system however, the presence of a sprinkler system only requires occupant notifications appliances activate upon sprinkler water flow.
2. The boiler room is considered an incidental use. Per table 509, a 1 hour separation is required or a sprinkler system. This is related to comment #1.

MECHANICAL REVIEW COMMENTS:
Approved

ELECTRICAL REVIEW COMMENTS
Approved

PLUMBING REVIEW COMMENTS:
Approved
07/27/2021 ROBERT SHERRY WATER REVIEW Completed
08/02/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM05553
750 N Alvernon Way – O-3
Building Expansion

TRANSMITTAL: August 2, 2021
This site is located in O-3 Zone (UDC 4.7.15), Medical Service Out Patient use is an allowed use in the zone (UDC Table 4.8-3) subject to Use Specific Standard 4.9.13.K.

1. Zoning has reviewed the building plans for compliance with DP21-0180 and although it appears that the building plans match the DP Zoning cannot approve the building plan until the DP is approved.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.
08/02/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/04/2021 JPEELDA1 FIRE REVIEW Reqs Change GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
Approved

BUILDING REVIEW COMMENTS:
Denied
1. The plans indicate that a sprinkler system is being installed. Is this just the expansion into the new space? Is there an existing alarm system? Ambulatory care facilities. Provide a narrative on the alarm system plans. Ambulatory care facilities require an alarm system however, the presence of a sprinkler system only requires occupant notifications appliances activate upon sprinkler water flow.
2. The boiler room is considered an incidental use. Per table 509, a 1 hour separation is required or a sprinkler system. This is related to comment #1.
09/02/2021 SBLOOD1 ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
09/02/2021 VVERA1 OUT TO CUSTOMER Completed