Permit Number: T21CM05552
Parcel: 10310001D

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T21CM05552
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/21/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Passed
07/28/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Passed
07/29/2021 JVINCEN1 FIRE REVIEW Approved
08/04/2021 SSHIELD1 ENGINEERING REVIEW Passed
08/11/2021 ELISA HAMBLIN ZONING REVIEW Denied From: Elisa Hamblin, AICP; Site Review Section Manager
Permit: T21CM05552; 19 N Silverbell Rd; Silverbell Public Improvement Electric Utility Relocation
Date: August 11, 2011

COMMENTS: The following comments are for the purpose of applying for a variance before the Board of Adjustment (UDC Article 3.10.1).

The proposal is for relocation and construction of electric utility equipment and transmission lines in relation to the widening of Silverbell Rd. This location is designated as a Scenic Corridor on adopted City maps and outlined in UDC Article 5.3. Per UDC Article 5.3.9.A. "All new utilities for development on private property and on public right-of-way along Scenic Routes shall be underground." As the proposed utilities are not proposed to be located underground, a Board of Adjustment Variance is required.

This permit may not be approved until a Variance is approved.

Please contact Mark.Castro@tucsonaz.gov for questions regarding the Variance process.
Please contact Elisa.Hamblin@tucsonaz.gov for questions regarding this transmittal.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/12/2021 VVERA1 OUT TO CUSTOMER Completed