Permit Number: T21CM05530
Parcel: 114512060

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM05530
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/02/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM05449/5523-5539

GENERAL:
? Provide written responses to all review comments.
? Provide a complete plan set.
? Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
Approved

BUILDING REVIEW COMMENTS:
Approved

MECHANICAL REVIEW COMMENTS:
Denied
1. Not complied, on your apartment unit mechanical plans, show where ceiling radiation dampers are to be installed in all apartment types, and your required to have ceiling radiation dampers not fire dampers as you have indicated on 6/M2
2. Not complied dryer duct is not in wall cavity in unit 6,5,4,etc. . it shall be protected in an approved manner (IMC2015,504.2)
3. Complied
4 Not complied It must be understood that table 403.3.1.1 of the IMC cannot be used without applying the equations in sections 403.3.1.1.1 through 403.3.1.1.2.3.4 (in your tables you have not calculated the fresh air required for the conference room or the exercise room, etc.) and Vot is the same as Voz it tells you how much outside air that unit must bring in based on your ventilation calculation cant have one without the other
5.Provide mechanical plan to show with sufficient clarity how the apartment units are penetrating the 1 hour horizontal ceiling membrane on the 1st floor (IMC2015,106.3.1)
6. please see attached mark ups on plans in narrative
ELECTRICAL REVIEW COMMENTS
Approved

PLUMBING REVIEW COMMENTS:
Approved
09/03/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
09/03/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM05449, T21CM05523, T21CM05524, T21CM05525, T21CM05526, T21CM05527, T21CM05528, T21CM05529, T21CM05530, T21CM05531, T21CM05532, T21CM05533, T21CM05534, T21CM05535, T21CM05536, T21CM05537, T21CM05538 & T21CM05539
2945 N Bear Canyon Rd – R-3
Multi-Family

TRANSMITTAL: September 3, 2021
This site is located in the R-3 zone (UDC Article 4.7.12). A multi-family is a permitted use in this zone (Table 4.8-2) subject to Use Specific Standards 4.9.7.B.6.

1. Until development package DP21-0174 has been approved Zoning cannot approve the building plans.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.
09/16/2021 SBLOOD1 ENGINEERING REVIEW Reqs Change The DP needs to be approved before the building plans can be approved.

Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.go
09/27/2021 ARUIZ1 PIMA COUNTY - ADDRESSING PIMA COUNTY - ADDRESSING Reqs Change PLEASE PROVIDE INDIVIDUAL BULDING NUMBER PRIOR TO PERMIT ISSUANCE.
addressing@pima.gov, 724-9512