Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T21CM05501
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/12/2021 | SBLOOD1 | ENGINEERING | REVIEW | Passed | |
| 07/19/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 07/21/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Replacement of up to 25% of the existing building fenestration will require that the U-factor and SHGC of the replacement fenestration be equal to or lower than the existing fenestration. Replacement of more than 25% of the fenestration will require the new fenestration to comply with the U-factor and SHGC values of the 2018 IECC. Reference: Section 5.1.3, exception (8), ASHRAE Standard 90.1-2016 and C402.4.3, IECC 2018. |
| 07/21/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 07/21/2021 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 07/28/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 07/29/2021 | JVINCEN1 | FIRE | REVIEW | Approved | |
| 08/02/2021 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 08/02/2021 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |