Permit Number: T21CM05438
Parcel: 128100770

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T21CM05438
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/14/2021 JVINCEN1 FIRE REVIEW Approved
07/21/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM05438

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
Conditionally Approved
Provide Top of Steel/Joists elevations for Low Roof, High Roof, High Point and Low Point and the Trellises on the Architectural or Structural Drawings. These elevations are not called out anywhere in the submitted drawings.

BUILDING REVIEW COMMENTS:
Denied
1. The occupancy group is not provided. Provide the occupancy class and correlate all requirements.
2. The construction type is not provided. Provide the construction type and correlate all requirements.
3. Due to the occupancy classification not being provided, the occupant load is incorrect. Provide a detailed occupant load calculation.
4. Correlate allowable square footages based on the comments above.
5. The cover page indicates that nonseparated mix use is being utilized, however, no other uses are listed as well no information listed.
6. Correlate plumbing requirements with comments above.
7. A complete review could not be completed until the comments above are addressed.
NOTE TO STAFF: Fee and Inspection Sheet will be completed upon resubmission.

MECHANICAL REVIEW COMMENTS:
Approved

ELECTRICAL REVIEW COMMENTS
Conditionally Approved
E3.0 LIGHTING PLAN: Cannot locate Sheet Note 5.
E5.0 SINGLE LINE DIAGRAM AND PANEL SCHEDULE: Show Electrical Fault locations F1 and F2 on Single Line Diagram.

PLUMBING REVIEW COMMENTS:
Denied
Review could not be completed until the building comments are addressed as those comments will drive the requirements throughout the rest of the project
07/22/2021 ROBERT SHERRY WATER REVIEW Completed
07/28/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM05438
5180 E Williams Ci
Building Expansions

TRANSMITTAL: July 28, 2021

This site is located in the PAD-1. Manufacturing – Heavy Equipment is not an permitted use in this zone (Table 4.8-5). Commercial Recreation is an allowed use in the PAD

1. As you are proposing and expansion of building a development package meeting the requirements of Administrative Manual 2-06 will need to be submitted and approved prior to approval of this building plan.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.
07/28/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
08/23/2021 SBLOOD1 ENGINEERING REVIEW Reqs Change See zoning comments for need of a DP

Final Status

Task End Date Reviewer's Name Type of Review Description
08/24/2021 NGARCIA3 OUT TO CUSTOMER Completed