Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/06/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Show the location of the gas meter on the plans. Reference: Section 107.2.1, IBC 2018. 2. Provide a complete diagram of the natural gas distribution system showing the all of the loads, developed lengths, and the layout of the distribution piping. Reference: Section 402.2, IFGC 2018. 3. Specify the materials used for the gas piping. Reference: Section 403.1, IFGC 2018. 4. Provide a tracer wire for any underground non-metallic gas piping. Reference: Section 404.17.3, IFGC 2018 |