Permit Number: T21CM05429
Parcel: 13621010B

Review Status: Completed

Review Details: OTHER

Permit Number - T21CM05429
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/06/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Show the location of the gas meter on the plans. Reference: Section 107.2.1, IBC 2018.
2. Provide a complete diagram of the natural gas distribution system showing the all of the loads, developed lengths, and the layout of the distribution piping. Reference: Section 402.2, IFGC 2018.
3. Specify the materials used for the gas piping. Reference: Section 403.1, IFGC 2018.
4. Provide a tracer wire for any underground non-metallic gas piping. Reference: Section 404.17.3, IFGC 2018

Final Status

Task End Date Reviewer's Name Type of Review Description
07/06/2021 NGARCIA3 OUT TO CUSTOMER Completed