Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T21CM05425
Parcel: 117170110

Address:
135 S 6TH AV #A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM05425
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/11/2021 SBLOOD1 ENGINEERING REVIEW Passed
07/14/2021 JPEELDA1 FIRE REVIEW Approved
07/15/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A1.0; Floor Plan: Please indicate on this plan all new partition walls, and provide notes/details indicating the wall stud size, gauge, spacing, and connections to the existing structure as required.
2. Sheets A1.1 and A1.2; Keynotes: Keynotes listed on these sheets are not indicated on the plans. Please provide.
3. General: Please provide written responses to all review comments.
07/20/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Show that the walk-in beer cooler meets the construction requirements of Section C403.10.2, IECC 2018.
2. Show that the walk-in beer cooler meets the efficiency requirements of Section C403.10.2.1, IECC 2018.
07/20/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide installation drawings for the new plumbing fixtures (e.g. hand sinks, pot filler) and services for the new appliances (e.g. Cheese Melter). Reference: Section 107.2.1, IBC 2018.
2. What are #K5.1 and #K6? Where is #K7? Reference: Section 107.2.1, IBC 2018.
3. Clarify the bar equipment list. What is new and what is existing? Reference: Section 107.2.1, IBC 2018.
4. Any new appliances (e.g. beverage dispensers, ice makers, etc.) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Section 608.14.1, IPC 2018 require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 608.1 and 608.3, IPC 2018.
07/20/2021 ROBERT SHERRY WATER REVIEW Completed
07/22/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
07/29/2021 IMONSHI1 ZONING REVIEW Approved
07/29/2021 IMONSHI1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed