Permit Number: T21CM05351
Parcel: 115155140

Review Status: Completed

Review Details: OTHER

Permit Number - T21CM05351
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/26/2021 PCAMARE1 OIP REVIEW Reqs Change FROM: Paul Camarena

PDSD Zoning Review Section




PROJECT: T21CM05351

Rooftop Solar Panels (1st Review)

826 W CALLE RETAMA




TRANSMITTAL DATE: July 26, 2021





COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.




COMMENT: Zoning has reviewed the plan and cannot approve it at this time. Please address the following comments.



o COMMENT: After comparing the aerials to the plot plan it has come to my attention that there is a possible non-permitted addition on the North portion of the house. After researching PRO there is an expired addition permit. In order to place the Solar panel on this addition, a "Finals only permit" will have to be obtained and finalized.




If you have any questions about this transmittal, Contact Paul Camarena any time during the week by email Paul.Camarena@Tucsonaz.gov



RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans

Final Status

Task End Date Reviewer's Name Type of Review Description
07/26/2021 NGARCIA3 OUT TO CUSTOMER Completed