Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T21CM05346
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/07/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 08/10/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | The specified Type I hood is not listed for use as an island hood. Removing the wall from the detail and not changing any of the hood specifications does not work. Specify a Type I island hood and include literature from the manufacturer showing the features and listings of the new hood. [Initial comment: A wall-mounted Type I canopy hood is specified but there is no wall adjacent to the hood. Provide a wall, coordinate with the architect. Reference: Section 304.1, IMC 2018.] |