Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T21CM05346
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/30/2021 | JVINCEN1 | FIRE | REVIEW | Approved | |
| 07/11/2021 | SBLOOD1 | ENGINEERING | REVIEW | Passed | |
| 07/15/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Structural Calculations; Sheet 6: The Tributary Width (TW) for the roof loading on the beam indicates 10'. That would include the roof uniform load from one side of the beam (the right side of the beam indicated on Sheet 6). The uniform roof loading from the left side of the beam should also be included in this calculation. Please verify. 2. Structural Calculations; Sheets 6 and 7: Revise the structural calculations to include the weight of a person working on the hood (maintenance). This will affect the point loads on Sheets 6 and 7. 3. General: Please provide written responses to all review comments. |
| 07/20/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | A wall-mounted Type I canopy hood is specified but there is no wall adjacent to the hood. Provide a wall, coordinate with the architect. Reference: Section 304.1, IMC 2018. |
| 07/20/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 07/22/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |