Permit Number: T21CM05346
Parcel: 10607004C

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM05346
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/30/2021 JVINCEN1 FIRE REVIEW Approved
07/11/2021 SBLOOD1 ENGINEERING REVIEW Passed
07/15/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Structural Calculations; Sheet 6: The Tributary Width (TW) for the roof loading on the beam indicates 10'. That would include the roof uniform load from one side of the beam (the right side of the beam indicated on Sheet 6). The uniform roof loading from the left side of the beam should also be included in this calculation. Please verify.
2. Structural Calculations; Sheets 6 and 7: Revise the structural calculations to include the weight of a person working on the hood (maintenance). This will affect the point loads on Sheets 6 and 7.
3. General: Please provide written responses to all review comments.
07/20/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
07/20/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change A wall-mounted Type I canopy hood is specified but there is no wall adjacent to the hood. Provide a wall, coordinate with the architect. Reference: Section 304.1, IMC 2018.
07/22/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved