| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/09/2021 | SBLOOD1 | ENGINEERING | REVIEW | Passed | |
| 07/14/2021 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | PDSD TRANSMITTAL FROM: PDSD Zoning Review PROJECT: T21CM05323 4140 N Fortune Lp New SFR attached (1st Review) TRANSMITTAL DATE: July 14, 2021 This site is located in the R-2 zone (UDC 4.7.8). A single-family residence is permitted use in this zone (Table 4.8-2) subject to Use Specific Standards 4.9.7.B.5 - .9. 1. As the Average Daily Traffic exceeds 140 this proposed dwelling does not qualify to use UDC Article 6.4.5.C.2.b.(2) therefor the required perimeter yard setback from the garage to the street property line is 18’, 19’ to back of sidewalk. If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov |
| 07/22/2021 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38. Provide the total developed length from meter to the most remote appliance on the system, and verify the size of the supply pipe for the connected demand (may require upgrading), G2413.3 & Table G2413.4(1). |