Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T21CM05316
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/14/2021 JPEELDA1 FIRE REVIEW Approved
07/14/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM05316

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
Denied
MILLER SALES AND ENGINEERING TENANT LAY OUT
1641 COMMERCE CT TUCSON ARIZONA.
1. REFER TO SHEET G100. ONLY ONE SERVICE SINK IS PROVIDED . HOWEVER, PER MECHANICAL CODES
EACH OCCUPANCY f1 AND BUSINESS REQUIRES ONE SERVICE SINK GOR EACH OCCUPANCY PER IPC
TABLE 403.1 (ONLY NOT REQUIRED IF OCCUPANCY LOAD IS LESS THAN 15).PLEASE PROVIDE AN
ADDITIONAL SERVICE SINK.
2. PROVIDE COMPLETE SITE PLAN WITH SHOWING NO OF PARKINGS PROVIDED. SHOW ON THIS PLAN
ACCESSIBLE PARKINGS PROVIDED. ALSO SPECIFY ACCESSIBALE ROUTE FROM AND TO BULIDING FROM
PARKING PLACE.PER ICC A117.1-2017 SECTION 502 AND SECTION 402.

BUILDING REVIEW COMMENTS:
Approved

MECHANICAL REVIEW COMMENTS:
Denied
1. Provide a detailed drawings and all manufactures specifications of the paint spray booth. Provide all calculations for all
systems in the spray booth. Show compliance with section 502.7 of the IMC.

ELECTRICAL REVIEW COMMENTS
Approved

PLUMBING REVIEW COMMENTS:
Approved
07/21/2021 ROBERT SHERRY WATER REVIEW Completed
07/27/2021 STEVE SHIELDS ZONING REVIEW Denied ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM05316
1641 W Commerce Ct
TI Manufacturing – Heavy Equipment

TRANSMITTAL: July 27, 2021

This site is located in the I-1 zone (UDC 4.7.29). Manufacturing – Heavy Equipment is not an permitted use in this zone (Table 4.8-5).

1. Based on UDC Article 11.3.5 INDUSTRIAL USE GROUP Definitions this use would be considered Heavy Equipment Manufacturing, The assembling or finishing of heavy machinery or equipment, such as automobiles, utility vehicles, aircraft, farming equipment, and utility trailers. Typical uses include auto assembly plants and tractor works which is not an allowed use in the I-1 Zone.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.
07/27/2021 SSHIELD1 ENGINEERING REVIEW Passed
07/27/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
07/27/2021 VVERA1 OUT TO CUSTOMER Completed