Permit Number: T21CM05314
Parcel: 10510010D

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM05314
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/28/2021 GSLEIGH1 PIMA COUNTY - ADDRESSING PIMA COUNTY - ADDRESSING Reqs Change Please contact Pima County Addressing, Suite #410 is not in our system. Verify suite #
07/11/2021 SBLOOD1 ENGINEERING REVIEW Passed
07/12/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
07/15/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
07/15/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
07/15/2021 ROBERT SHERRY WATER REVIEW Completed
07/21/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.

The electrical floorplan and panel schedules do not correlate with the Mechanical and Plumbing equipment. For example; the power for the Insta-hot and Mechanical equipment is not shown. Please clarify.

Ref; 2018 IBC sec 107.2.1, 2017 NEC.

City of Tucson Commercial Plan Submittal Requirements
07/27/2021 STEVE SHIELDS ZONING REVIEW Approved
07/27/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/29/2021 JVINCEN1 FIRE REVIEW Approved