Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T21CM05293
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/16/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Previous Comment 1; General: All drawings must be sealed, signed, and dated by a registered design professional. |
| 08/23/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments and provide a written response. Ref; Plan Sheet PV3, PV4, PV4.1. The new Hoffman Box is not shown on plan PV3. Depending on distances it may be necessary to increase the feeder size between the Hoffman Box and the existing 200 amp Sub- Panel. NEC 240.21, 705.12B. Indicate sizes and types for the feeders between the New Hoffman Box and the existing Sub Panel and also between the existing electrical service panel and the New Hoffman Box. Why are some of the electrical plans not sealed by the Registrant of Record? Ref; 2018 IBC sec. 107.2.1, 2018 NEC, City of Tucson Commercial Plan Submittal Requirements. |