Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T21CM05293
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/13/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. General: All drawings must be sealed, signed, and dated by a registered design professional. 2. General: Please provide structural calculations indicating the existing roof framing is capable of supporting the new PV system. These calculations must be sealed, signed, and dated by a registered design professional. |
| 07/20/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following Electrical plan review comments. Also provide a written response. Provide Sealed electrical plans, design and calculations performed by an Arizona registrant who has demonstrated proficiency through registration, education, technical knowledge, or experience to perform such work. Ref; 2018 IBC 107.2.1, 2017 NEC. City of Tucson Commercial Plan/Permit Submittal Requirements. |
| 07/27/2021 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 07/29/2021 | SBLOOD1 | ENGINEERING | REVIEW | Passed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/30/2021 | VVERA1 | OUT TO CUSTOMER | Completed |