Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T21CM05286
Parcel: 117041080

Address:
621 N 6TH AV

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T21CM05286
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/03/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

1. Per the revision letter submitted, the existing 3 phase electrical service located at Building #1 is to be changed to a single-phase service and also feeds panel ‘P2’via panel ‘P1’ . Ref; Plan sheet E300.2. The panel schedule for panel ‘P1’ shows a 400 amp rated panel with a 100 amp MCB. This is undersized for the calculated load. Please revise the panel schedule showing the correct MCB rating.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, 2012 Tucson/Pima County outdoor Lighting Code.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/04/2022 VVERA1 OUT TO CUSTOMER Completed