Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T21CM05286
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/03/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments and provide a written response. 1. Per the revision letter submitted, the existing 3 phase electrical service located at Building #1 is to be changed to a single-phase service and also feeds panel ‘P2’via panel ‘P1’ . Ref; Plan sheet E300.2. The panel schedule for panel ‘P1’ shows a 400 amp rated panel with a 100 amp MCB. This is undersized for the calculated load. Please revise the panel schedule showing the correct MCB rating. Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, 2012 Tucson/Pima County outdoor Lighting Code. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/04/2022 | VVERA1 | OUT TO CUSTOMER | Completed |