Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T21CM05286
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/06/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. General: Please provide an enlarged, dimensioned floor plan for the restroom and indicate the grab bars per the ICC/ANSI A117.1 Figures 604.5.1 and 604.5.2. |
| 07/08/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Comment not addressed. [Initial comment: Changing from a massage use to a beauty salon use requires additional ventilation, including required exhaust. Reference: Section 403.3.1, IMC 2018.] |
| 07/08/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Coordinate the water heater detail, 3/P300.2, with the plumbing design for building 2 (e.g. building 2 plumbing design does not have a recirculating hot water system). Reference: Section 107.2.1, IBC 2018. |
| 07/08/2021 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 07/09/2021 | SBLOOD1 | ENGINEERING | REVIEW | Passed | |
| 07/20/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 07/27/2021 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 07/27/2021 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 07/30/2021 | JVINCEN1 | FIRE | REVIEW | Approved |