Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T21CM05255
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/14/2021 JPEELDA1 FIRE REVIEW Approved
07/14/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM05255

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
Approved

BUILDING REVIEW COMMENTS:
Approved

MECHANICAL REVIEW COMMENTS:
Denied
1.. boilers shall be interlocked to mechanical combustion air, to prevent main burner operation when the mechanical air supply system is not in operation (IFGC2018,304.9.2)
2.. Boilers shall be csd-1 certified (IMC2018,1006.7)
3. Where the serving gas supplier delivers gas at a pressure greater than 2 psi for piping systems serving appliances designed to operate at a gas pressure of 14 inches w.c. or less, overpressure protection devices shall be installed. Piping systems serving equipment designed to operate at inlet pressures greater than 14 inches w.c. shall be equipped with overpressure protection devices as required by the appliance manufacturer’s installation instructions (IMC2018,416.1)

ELECTRICAL REVIEW COMMENTS
Approved

PLUMBING REVIEW COMMENTS:
Approved
07/19/2021 ROBERT SHERRY WATER REVIEW Completed
07/23/2021 STEVE SHIELDS ZONING REVIEW Approved
07/23/2021 SSHIELD1 ENGINEERING REVIEW Passed
07/23/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
07/23/2021 VVERA1 OUT TO CUSTOMER Completed