Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T21CM05252
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/04/2022 | RPARSON1 | OIP | REVIEW | Completed | FROM: Name PDSD Residential Review Section PROJECT: T21CM05252 Roof top Solar Panels 2256 E Jasmine Dr. TRANSMITTAL DATE: February 16, 2022 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Residential Review Section comments were addressed. COMMENT: Residential has reviewed the plan and cannot approve at this time. Please address the following comments COMMENT: The Plan Set shows a line-side tap, Line taps require compliance with NEC 230.46. Update the plans showing a tap enclosure with sufficient space for the tap device, or show a meter socket extension with tap terminals (approved Milbank tapping device) COMMENT: Residential will review the application on the next submittal If you have any questions about this transmittal, Contact Robert Parsons Robert.Parsons@Tucsonaz.gov any time during the week by email. RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/16/2022 | NGARCIA3 | OUT TO CUSTOMER | Completed |