Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T21CM05237
Parcel: 11705047B

Address:
416 N HERBERT AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM05237
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/07/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A1.0; Code Review Checklist: The checklist indicates this is a B Occupancy Group. The floor plan on Sheet A2.0 indicates the workshop area as the predominant function space. Please revise the checklist to indicate the Occupancy Classification as F1 or F2.
2. Sheet A1.0; Code Review Checklist: Please revise the Occupant Load for this space using Table 1004.5.
3. Sheet A2.0; Wall Types: Please indicate the gauge of the metal wall studs in Wall Types B and C.
4. Sheet A2.0; Interior Restroom Elevations: Please add dimensions to Elevations A and B per the ICC/ANSI Figures 604.5.1 and 604.5.2.
5. General: Please provide written responses to all review comments.
07/12/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change If the condensing unit is not located in a controlled space, provide locking access port caps for the condensing unit per Section 1101.10, IMC 2018.
07/12/2021 ROBERT SHERRY WATER REVIEW Completed
07/13/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. If the occupancy of the space is changed from B to F1 or F2, provide drinking fountains for the building. Reference: Section 2902.1, IBC 2018. And Section 410.3, IPC 2018.
2. Provide an approved vacuum relief valve for the scheduled bottom-fed water heater that is located above the fixture outlets. Reference: Section 504.2, IPC 2018.
3. Show the size, route, and termination of the T&P relief piping and the drain line from the pan. Reference: Section 504, IPC 2018.
4. Termination of the excess pressure relief from a water heater over an elevated service sink is not an approved location. Reference: Section 504.6 (6), IPC 2018.
5. Revise the design of the hot water piping so that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018.
07/14/2021 JPEELDA1 FIRE REVIEW Approved
07/19/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.

Provide complete compliance with the 2012 Tucson/Pima County Outdoor Lighting Code for the exterior lighting within this parcel. Include all lighting, including existing in the lumen calculations.

See section 104 for Plan Submittal Requirements.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2012 Tucson/Pima County Outdoor Lighting Code (OLC),

City of Tucson Commercial Plan Submittal Requirements
07/26/2021 SSHIELD1 ENGINEERING REVIEW Passed
07/26/2021 STEVE SHIELDS ZONING REVIEW Approved
07/26/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed