Review Date Reviewer's Name Type of Review Description Status Comments
08/04/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following Electrical plan review comments. Also provide a written response.

In reference to the response for electrical review comment # 3. The plan needs to provide evidence that the site exterior lighting is in full compliance with the Outdoor Lighting Code (OLC), section 104.2.

It appears from the electrical site plan that the location that the 18’ high light poles closest to the residential property are to close to the site property boundary to meet the height limitations as outlined in section 401.3.1. Provide evidence on the site plan that the exterior light poles meet these height restrictions as well as providing House Side Shields required per section 401.3.2.

Ref; 2018 IBC 107.2.1, 2017 NEC. City of Tucson Commercial Plan/Permit Submittal Requirements. 2012 Tucson/Pima County Outdoor Lighting Code.