Permit Number: T21CM05180
Parcel: 131130490

Address:
6141 E 33RD ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T21CM05180
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/23/2021 SBLOOD1 ENGINEERING REVIEW Passed
07/13/2021 LSHAMIS1 ZONING REVIEW Reqs Change CDRC Transmittal

FROM: Loran Shamis
PDSD Zoning Review Section

PROJECT: T21CM05180
Mezquita Residence Addition (1st Review)
6141 E 33RD ST

TRANSMITTAL DATE: July 13, 2021

DUE DATE: July 9, 2021

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

Single family residential is permitted in the R-1 zone, use-specific standards 4.9.7.B.5 - .9 are applicable.

01. COMMENT: Include the distance between the proposed addition to the adjacent parcel line. The minimum required setback is 6' or 2/3 the height of the adjacent wall, the greater applies, measured from the exterior, adjacent wall to the parcel line. See plot plan example:
https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf

02. COMMENT: Demonstrate the height of the exterior wall on the western façade and the northern façade to review for minimum setback requirements. See plot plan example.

If you have any questions about this transmittal, Contact Loran Shamis at Loran.Shamis@tucsonaz.gov.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans
07/20/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T21CM05180
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

SITE PLAN:

1. Show an existing or upgraded 1” yard line to the building. Minimum size for a pipe supplying two bathrooms within the building is 1”, P2903.7.

MECHANICAL PLANS:

1. Show bathroom (without a window) exhaust fan locations with minimum 50 CFM rating and duct to the exterior, R303.3 and M1505.

ELECTRICAL PLANS:

1. Interior alterations require the installation of smoke alarms at existing bedrooms, R314.2.1. Provide notation if the bedroom smoke alarms are existing or proposed.

If you have any questions, please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review