Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T21CM05144
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/13/2022 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 04/19/2022 | JVINCEN1 | FIRE | REVIEW | Reqs Change | 1. Submit HMIS. Please refer to IFC 407.5, 5001.5.2., and Appendix H. 2. Submit HMMP. Please refer to IFC 407.6, 5001.5.1., and Appendix H. 3. The weight of ethanol on cover sheet is incorrect. Make corrections. 4. Add a note to deferred submittals. Continuous gas detection alarm required in extraction room. Please refer to IFC section 3905, entire section. John Vincent john.vincent@tucsonaz.gov 5203495581 |