Permit Number: T21CM05144
Parcel: 140420980

Address:
2380 E MEDINA RD

Review Status: Completed

Review Details: 3RD PARTY REVIEW - COMMERCIAL TI

Permit Number - T21CM05144
Review Name: 3RD PARTY REVIEW - COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/04/2022 STANTEC 3RD PARTY REVIEW-COMMERCIAL REVIEW Completed
04/04/2022 DBENOIT1 3RD PARTY REVIEW-COMMERCIAL AT 3RD PARTY OFFICE Completed
07/13/2021 ROBERT SHERRY WATER REVIEW Completed
07/19/2021 SSHIELD1 ENGINEERING REVIEW Passed
07/19/2021 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/19/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM05144
2380 E Medina Rd
Medical

TRANSMITTAL: July 19, 2021
This site is located in the I-1 zone (UDC 4.7.29). Marijuana Dispensary Off-Site Cultivation Location is an allowed use in the zone subject to Use Specific Standards 4.9.9.E.2 and 4.9.13.Q.

1. Clearly demonstrate how the requirements of UDC Article 4.9.9.E.2.k are met.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.
08/18/2021 JVINCEN1 FIRE REVIEW Reqs Change -Include (HMIS) hazardous materials inventory statement. Include all chemicals, compressed gases, etc...
Product name, component, chemical abstract number, location where stored or used, container sizes, hazard classifications, amount in storage, amount in use-closed systems, amount in use-open systems.
-Remove/correct deferred submittal information about ansul system. I'm assuming you meant fire sprinkler system and not ansul system. Page G1.0
-Indicate if building has a fire alarm.
-Indicate if carbon dioxide enrichment system will be used now or in the future. If used, separate permits will be required for operation and installation of gas detection alarm. The gas detection alarm is a deferred submittal and shall be added to the deferred submittals on page G1.0. Installation of CO2 enrichement system will require mechanical ventilation upon activation. Also provide all CO2 documentation IFC 5307.4.1. See IFC 5307.4 for all requirements.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/04/2022 NGARCIA3 OUT TO CUSTOMER Completed