Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T21CM05113
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/05/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Provide a structural detail that is based on the structural calculations and clearly shows how the wall is to be modified and the platform is to be attached to the wall. [Second comment: The capability of the Holdrite platform is not in doubt. The question is how will the platform be attached to the wall and is the wall structurally able to support the water heater?] [Initial comment: Provide structural calculations and details for attaching the mounting shelf for the water heater to show that the water heater will be safely supported from the building structure. Reference: Section 301.2, IPC 2018.] |