Permit Number: T21CM05113
Parcel: Unknown

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM05113
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/24/2021 JPEELDA1 FIRE REVIEW Approved
06/29/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A6.0; Break Room Elevation 11: The sink height above finish floor in the Break Room indicates 3'-0". The Break Room is considered a common use area (especially providing the route to the accessible restroom), and therefore, per the ICC/ANSI Section 606.3, must have a maximum sink height of 34". Please revise.
2. Sheet A6.0; Key Plan: All of the interior elevation indicators on this plan reference Sheet A7.0. Please revise that reference.
07/06/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Correct the exhaust fan schedule to show that EF-1 serves the procedure room. Reference: Section 107.2.1, IBC 2018.
2. The procedure room appears to be ventilated as an animal area. Recirculation of air from animal areas to other occupancy types is prohibited. Reference: Section 403.2.1 and footnote b, Table 403.3.1.1, IMC 2018.
07/06/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide structural calculations and details for attaching the mounting shelf for the water heater to show that the water heater will be safely supported from the building structure. Reference: Section 301.2, IPC 2018.
2. Provide a lint separator for the commercial washer. Reference: Section 1003.6, IPC 2018.
07/06/2021 ROBERT SHERRY WATER REVIEW Completed
07/13/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
07/16/2021 JGARCIA1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/19/2021 SSHIELD1 ENGINEERING REVIEW Passed
07/19/2021 STEVE SHIELDS ZONING REVIEW Approved