Permit Number: T21CM05081
Parcel: 14043013D

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T21CM05081
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/25/2021 JVINCEN1 FIRE REVIEW Approved
07/12/2021 ROBERT SHERRY WATER REVIEW Completed
07/14/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM05081

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
Approved

BUILDING REVIEW COMMENTS:
Approved

MECHANICAL REVIEW COMMENTS:
1. All rooms to the building shall be in ventilation calculation table. (e.g. missing parts room ,sheet metal shop, stock room, avionics lab, quality assurance room #113. (IMC2018,403.3.1.1)
2. Provide duct smoke detectors to EC#2&EC#3 (IMC2018,606.2)
3. Provide duct smoke detectors to heat pump's #3&4 which share a common outside air duct to the return of both units (IMC2018,606.2.2)
4. Spray painting shall not be conducted in the same building but in a separate detached building (IBC2018,412.4.5)
5. Provide quantity and type of hazardous chemical in ,106.3.1)the metal shop room (IMC2018,106.3.1)
6. Carbon monoxide detector shall initiate at 25 ppm not 35 ppm (IMC2018,404.1)
7. Provide quantity and type of hazardous chemical in the sheet metal shop room (IMC2018,106.3.1)

ELECTRICAL REVIEW COMMENTS
Denied
E-601 ELECTRICAL DETAILS: Detail 1 calls out for Volcanic fill for Test Well. Is this required?
Typically, volcanic material does not assure good grounding.
E-602 ELECTRICAL DETAILS: Confirm ground rod is not required for exterior light poles.
E-701 ELECTRICAL ONE-LINE DIAGRAMS: Call out incoming from TEP Utility feed.

PLUMBING REVIEW COMMENTS:
Approved
07/15/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM05081
1920 E Aero Park Blvd.
New Hanger

TRANSMITTAL: July 15, 2021
This site is located in the I-2 zone (UDC 4.7.30).

1. Zoning has reviewed the building plan for compliance with DP21-0153 and although it appears that the building plans match the DP Zoning cannot approve the building plans until the DP is approved.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.
07/15/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
07/29/2021 SBLOOD1 ENGINEERING REVIEW Reqs Change The DP needs to be approved before the building plans

Final Status

Task End Date Reviewer's Name Type of Review Description
07/29/2021 VVERA1 OUT TO CUSTOMER Completed