Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T21CM05081
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/25/2021 | JVINCEN1 | FIRE | REVIEW | Approved | |
| 07/12/2021 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 07/14/2021 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T21CM05081 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Approved BUILDING REVIEW COMMENTS: Approved MECHANICAL REVIEW COMMENTS: 1. All rooms to the building shall be in ventilation calculation table. (e.g. missing parts room ,sheet metal shop, stock room, avionics lab, quality assurance room #113. (IMC2018,403.3.1.1) 2. Provide duct smoke detectors to EC#2&EC#3 (IMC2018,606.2) 3. Provide duct smoke detectors to heat pump's #3&4 which share a common outside air duct to the return of both units (IMC2018,606.2.2) 4. Spray painting shall not be conducted in the same building but in a separate detached building (IBC2018,412.4.5) 5. Provide quantity and type of hazardous chemical in ,106.3.1)the metal shop room (IMC2018,106.3.1) 6. Carbon monoxide detector shall initiate at 25 ppm not 35 ppm (IMC2018,404.1) 7. Provide quantity and type of hazardous chemical in the sheet metal shop room (IMC2018,106.3.1) ELECTRICAL REVIEW COMMENTS Denied E-601 ELECTRICAL DETAILS: Detail 1 calls out for Volcanic fill for Test Well. Is this required? Typically, volcanic material does not assure good grounding. E-602 ELECTRICAL DETAILS: Confirm ground rod is not required for exterior light poles. E-701 ELECTRICAL ONE-LINE DIAGRAMS: Call out incoming from TEP Utility feed. PLUMBING REVIEW COMMENTS: Approved |
| 07/15/2021 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | ZONING REVIEW TRANSMITTAL FROM: PDSD Zoning Review PROJECT: T21CM05081 1920 E Aero Park Blvd. New Hanger TRANSMITTAL: July 15, 2021 This site is located in the I-2 zone (UDC 4.7.30). 1. Zoning has reviewed the building plan for compliance with DP21-0153 and although it appears that the building plans match the DP Zoning cannot approve the building plans until the DP is approved. If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov. |
| 07/15/2021 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 07/29/2021 | SBLOOD1 | ENGINEERING | REVIEW | Reqs Change | The DP needs to be approved before the building plans |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/29/2021 | VVERA1 | OUT TO CUSTOMER | Completed |