Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T21CM05041
Parcel: 11301146Z

Address:
1821 E PRINCE RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM05041
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/23/2021 JPEELDA1 FIRE REVIEW Approved
06/28/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
07/01/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restrooms will be exhausted (i.e. all of the air supplied to each restroom is to be exhausted during the hours of operation even if the lights are off). The exhausted air from the restrooms shall be limited to no more than 10% of any subsequent supply air stream. Reference: Section 403.2.1 (4), IMC 2018.
07/01/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide a metering faucet for the lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10-seconds. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
2. Provide tempered water for the public restroom lavatory using an approved device conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2018.
07/01/2021 ROBERT SHERRY WATER REVIEW Completed
07/12/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response. #1. Please provide complete compliance with the 2018 IECC for the lighting.
07/15/2021 SSHIELD1 ENGINEERING REVIEW Passed
07/15/2021 STEVE SHIELDS ZONING REVIEW Approved
07/15/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
08/03/2021 VFLORES1 APPROVAL SHELF Completed
08/03/2021 VFLORES1 OUT TO CUSTOMER Completed
08/03/2021 VFLORES1 REJECT SHELF Completed