Permit Number: T21CM05018
Parcel: 10511061R

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM05018
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/26/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The plumbing supply riser does not appear to show the circulating hot water loop (i.e. the hot water source) being within 24-inches of the lavatory stop valves. Revise the riser diagram to show the loop dropping down in the wall so that the ½-inch hot water branches to the lavatories are no longer than 24-inches. [Initial comment: Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018 (i.e. 24-inches for ½-inch pipe).]